Fieldbus - ABB PST Installation And Maintenance Manual

Table of Contents

Advertisement

Settings
Functional settings
Figure 30: Fieldbus group
88
AC 1006.9 - 5/03
Chapter 7 - Settings and configuration
Start / Stop
Protections
Warnings
Faults
Inputs
Outputs

Fieldbus

Seq. Start
Fieldbus
To set parameters related to the fieldbus communication,
enter the Fieldbus group.
Fieldbus control (Fieldb Ctrl)
Activate the fieldbus control by changing to Yes .
Press Store to save the selected function.
Fieldbus type (Fieldb Type)
Select what fieldbus type is used.
AS-I
Used for AS-I protocol.
Other
Used for protocols other than AS-I (i.e.,
DeviceNet, Profibus DP, Modbus).
Press Store to save/activate the selected function.
Fieldbus address (Fieldb Addr)
Set a unique address number between 1 and 1000 for
fieldbus communication.
Press Store to save the selected function.
Warning!
If the motor is running and the parameter Fieldb Ctrl is
changed from No to Yes, this will stop the motor (fieldbus
control overrides the programmable inputs).
If the motor is not running and the parameter Fieldb Ctrl is
changed from Yes to No, this might start the motor if there is
a start signal present.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pstb

Table of Contents