Chapter 5 - Connection

5:2.2.4 Programmable inputs, terminals 6 and 7

The softstarter has two programmable inputs.
In0: default, reset, fault/overload.
In1: default, reset, fault/overload.
See Chapter 7 " Settings and configuration" for programming.
Connect the cables according to Figure 17 or Figure 18 depending on whether
the internal or external source is being used.
M3
0.5 Nm - 4.3 lb.in
Figure 18: External control voltage
3.5x0.6
0.14 ... 2.5 mm
2
AWG 12 ... 22
0.14 ... 2.5 mm
2