If necessary, the default parameter values can be restored by parameter
Parameter
restore.
Settings and diagnostics
Parameters:
96.06 Parameter restore...96.07 Parameter save
Events: -

Control interfaces

Programmable analog inputs

There are two programmable analog inputs. Each of the inputs can be independently
set as a voltage (0/2...10 V) or current (0/4...20 mA) input by parameter. Each input
can be filtered, inverted and scaled. AI1 can be configured as DI5 by parameter.
Settings and diagnostics
Parameter group
12 Standard AI
Events: -

Programmable analog outputs

There is one analog output voltage (0/2...10 V) or current (0/4...20 mA) output (can
be set by parameter). The output can be filtered, inverted and scaled.
Settings and diagnostics
Parameter group
13 Standard
Events: -

Programmable digital inputs and outputs

There are four digital inputs, and one digital outputs. In addition, the analog input AI1
can be configured as digital input DI5 by a parameter.
Digital inputs DI3 and DI4 can be used as frequency input.
Settings and diagnostics
Parameter groups
Events: -

Programmable relay outputs

There is one relay output. The signal indicated by the output can be selected by a
parameter.
and
AO.
10 Standard DI, RO
11.21 DI5
configuration.
and
11 Standard DIO, FI,
Program features 49
96.06
manually.
FO.