140
AC 1006.9 - 5/03
Chapter 10 - Functions
10:44 Phase loss fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/Ph Loss Op
This parameter makes it possible to select between two different
actions if a phase loss fault occurs.
Stop– M
Stop– A
10:45 Fieldbus fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/FB Fault Op
This parameter makes it possible to select between two different
actions if a fault occurs in the fieldbus communication.
Stop– M
Stop– A
The motor stops and a manual reset is
required before restart.
The motor stops and an automatic reset
is performed when the fault disappears.
Parameter
Default
text
value
Ph Loss Op Stop-M
The motor stops and a manual reset is
required before restart.
The motor stops and an automatic reset
is performed when the fault disappears.
Parameter
Default
text
value
FB Fault Op Stop-M
Setting
Description
range
Type of
Stop-M,
operation for
Stop-A
phase loss
fault
Setting
Description
range
Type of
Stop-M,
operation for
Stop-A
fieldbus fault