Time(s)
1000
100
10
1
1
2
3
Figure 8: Tripping curves for the
electronic overload
A
Class 30
B
Class 20
C
Class 10
D
Class 10A
126
AC 1006.9 - 5/03
Chapter 10 - Functions

10:14 Overload class

A
B
C
D
4
5
6
Current
(x I e )

10:15 Overload class, dual type, start class

Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Overload/OL Class
This parameter makes it possible to set the required overload class.
Four different classes are available according to Figure 8.
Class 10A
Class 10
Class 20
Class 30
Parameter
Default
text
value
OL Class
10
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Overload/Dual Class S
This parameter makes it possible to set the required overload class
during start. When full voltage is reached, there will be a switch-over
to run class (see below).
Parameter
Default
text
value
OL Class S
10
Setting
Description
range
10A, 10, 20,
Overload
30
class
Setting
Description
range
10A, 10, 20,
Overload
30
class