Chapter 8 - Fieldbus communication (option)

8:1.3.1 Binary input telegram

To PLC from Softstarter.
Word in
Binary
input
input
Bit
data area
byte
0
0
0
1
2
3
4
5
6
7
1
8 (0)
9 (1)
10 (2)
11 (3)
12 (4)
13 (5)
14 (6)
15 (7)
1
2
0
1
2
3
4
5
6
7
3
8 (0)
9 (1)
10 (2)
11 (3)
12 (4)
13 (5)
14 (6)
15 (7)
2
4
0
1
Data
K4 relay output
K5 relay output
K6 relay output
V7 Programmable software
output
Start Input
Stop Input
In0 Input
In1 Input
Run
Top Of Ramp
Line or Inside Delta
connection
Phase sequence
Prot Motor OL
Prot Locked Rot
Prot Underload
Prot Phase Imb
Prot High I
Prot Phase Rev
Prot PTC
Fault ByPass
Prot SCR OL
Warn OL
Warn SCR OL
Warn I=High
Warn I=Low
Fault (general signal)
Fault Phase Loss
Fault SC SCR
Fault Open SCR
Fault Wrong Freq
Fault Connection
Fault Internal
Fault FB Timeout
Fault HS Temp
Description
Status of K4
Status of K5
Status of K6
Status of V7
Status of Start Input
Status of Stop Input
Status of In0
Status of In1
Run Status
Top Of Ramp Status
0 = Line, 1 = Delta
0 = L1,L2,L3 1=L1,L3,L2
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status, general for all
faults
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status
Event Status
AC 1006.9 - 5/03