Status
Underload protection
Power on
Prot Underload
Reset
Locked rotor protection
Power on
Prot Locked Rot
Reset
High current protection
Power on
Prot High I
Reset
Phase imbalance protection
Power on
Prot Phase Imb.
Reset
Phase reversal protection
Power on
Prot Phase Rev
Reset
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Chapter 11 - Troubleshooting
Possible cause
The motor current is below set
level and time.
Fault
Protection
Back
The motor is running stiff for some
reason.
A damaged bearing or a stuck
load could be possible causes.
Fault
Protection
Back
A fault current, higher than 8 times
the softstarter rating has occurred.
Fault
Protection
Back
Unbalance in the phase currents.
Fault
Protection
Back
The phase sequence is not
correct.
Fault
Protection
Back
Solution
• Check and correct the reason for
the underload.
• Check that the settings are
according to the operation
conditions.
• Check the bearings of the motor
and load.
• Check that the load is not running
stiff.
• Check the circuits including the
motor for any insulation fault, phase
to phase or ground fault.
• Check the main voltage and the
motor circuit.
• Restart the motor and check the
phase currents.
• Check the phase sequence on the
line side to (L1-L2-L3).
165