ABB PST Installation And Maintenance Manual page 80

Table of Contents

Advertisement

80
AC 1006.9 - 5/03
Chapter 7 - Settings and configuration
Phase reversal (Phase Rev)
Activate the phase reversal protection if required by chang-
ing to Yes .
If "Yes" is selected, the following setting will be available:
Phase reversal type of operation (Ph Rev Op)
Select what operation should be initiated if the phase
reversal protection is activated:
Stop– M The motor will stop and a manual reset is required.
Stop– A The motor will stop and an automatic reset is
performed.
Ind
Only indication will be given.
Press Store to save the selected operation.
PTC
Activate the PTC protection if required by changing to Yes .
If "Yes" is selected, the following setting will be avail-
able:
PTC type of operation (PTC Op)
Select what operation should be initiated if the PTC protec-
tion is activated:
Stop– M The motor will stop and a manual reset is required.
Stop– A The motor will stop and an automatic reset is
performed.
Ind
Only indication will be given.
Press Store to save the selected operation.