Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Chapter 10 - Functions
10:57 Initial voltage, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Init Volt1
This parameter makes it possible to set the initial voltage for the first
parameter set.
Parameter
text
Init Volt1
10:58 Current limit, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Curr Lim1
This parameter makes it possible to set the current limit level for the
first parameter set.
Parameter
text
Curr Lim1
10:59 Setting current, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./1st Set Ie
This parameter makes it possible to set the rated motor current for
the first parameter set.
Parameter
text
1st Set Ie
Default
Setting
value
range
30%
30... 70%
Default
Setting
value
range
4 x I
2.0... 5.0xI
e
Default
Setting
value
range
9... 1380A
divided into
Ir
19
overlapping
ranges
Description
First
sequence,
initial voltage
for start
ramp
Description
First
sequence,
e
current limit
Description
First
sequence,
current limit
AC 1006.9 - 5/03
149