Analog Output Telegram; Input Address Map - ABB PST Installation And Maintenance Manual

Table of Contents

Advertisement

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Chapter 8 - Fieldbus communication (option)

8:1.3.5 Analog output telegram

From PLC to Softstarter.
All analog data will be represented as 16 bit values.
Word in
Analog
output
output
data area
word
1
0
2
1
3
2
4
3
5
4
6
5
The output data is used to synchronize the softstarter real time clock with a
system clock.
It is used together with the binary output time synchronisation signal. If this
signal is set to "1" and there is a difference between the clocks, the local
softstarter clock will be synchronised with the analog outputs.

8:1.3.6 Input address map

15 14 13 12 11 10 9
Binary In, Byte 1
0
Binary In, Byte 3
1
Binary In, Byte 5
2
Analog In, Word 0
3
4
Analog In, Word 1
Analog In, Word 2
5
Analog In, Word 3
6
7
Analog In, Word 4
Analog In, Word 5
8
Analog In, Word 6
9
Analog In, Word 7
10
Analog In, Word 8
11
Diagn. Channel 1, Error Code
12
Diagn. Channel 2, Error Code
13
14
Diagn. Channel 3, Error Code
Data
Representation
Year
Value = 2003 » Year 2003
Month
Value = 12 » December
Day
Value = 31 » 31st
Hour
Value = 23 » 23 h
Minutes
Value = 59 » 59 min
Seconds
Value = 59 » 59 sec
8
7
Binary In, Byte 0
Binary In, Byte 2
Binary In, Byte 4
Diagn. Channel 1, Parameter No
Diagn. Channel 2, Parameter No
Diagn. Channel 3, Parameter No
6
5
4
3
2
1
0
107
AC 1006.9 - 5/03