Settings
Functional settings
Figure 28: Inputs group
84
AC 1006.9 - 5/03
Chapter 7 - Settings and configuration
Start / Stop
Protections
Warnings
Faults

Inputs

Outputs
Fieldbus
Seq. Start
7:2.4.5 Inputs
To set parameters related to the programmable inputs,
enter the Inputs group.
First programmable input (In0)
Select the required function for the input In0.
Press Store to save/activate the selected function.
One of the following functions can be selected:
None
No specific function (not activated).
Reset
Reset of a fault or overload condition.
Enable
When In0=0 the softstarter stops immedi-
ately.
When In0=1 the softstarter is in normal
operation.
Overrides all other inputs.
Jog
Performs a start ramp until command is
released. The motor stops immediately
when the input is opened.
DOL
Open/close the bypass contactor
(PSTB370...PSTB1050).
Start2
Start signal for 2nd parameter set-up.
Press Store to save/activate the selected function.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com