Chapter 10 - Functions
10:24 Underload protection time
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Underload/Underl Time
This parameter makes it possible to set the delay time from detec-
tion until the protection is activated. It is active only if underload
protection is selected
Parameter
text
Underl Time 10 s
10:25 Underload protection, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Underload/Underl Op
This parameter makes it possible to select between three different
actions when the protection is activated. It is active only if the
underload protection is selected.
Stop– M
Stop– A
Ind
Parameter
text
Underl Op
Default
Setting
value
range
1... 30 s
The motor stops and a manual reset is
required before restart.
The motor stops and an automatic reset
is performed when the fault disappears.
The motor continues to run but a fault
indication is given.
Default
Setting
value
range
Stop-M,
Stop-M
Stop-A, Ind
Description
Trip time for
Underload
protection
Description
Type of
operation for
Underload
protection