ABB PST Installation And Maintenance Manual page 69

Table of Contents

Advertisement

Setting Ie
100A
Store
Figure 14: Setting Ie menu
Setting Ie
100A
Next
Back
Figure 15: Confirming Setting Ie
OL Class
10
Store
Figure 16: Overload class
OL Class
10
Next
Back
Figure 17: Confirming OL Class
Ext ByPass
Yes
Store
Figure 18: Confirming OL Class
Ext ByPass
Yes
Next
Back
Figure 19: Confirming OL Class
Ready?
Yes
Tune Set
Figure 20: Ready?/Tune Set menu
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Chapter 7 - Settings and configuration
Setting I
(motor FLA)
e
Set the motor full load current (i.e. rated motor current if the
unit is connected In Line).
For units connected Inside Delta, the Setting I
according to the current in the delta circuit = 58%
the rated motor current.
Press Store to save the data after setting the current.
Confirm the Setting I
by pressing Next . If the wrong value is
e
set, press Back and set the correct value.
Overload class (OL Class)
Select the desired overload class. Available classes:
10
10A
20
30
Press Store to save the selected class.
Confirm the selected overload class by pressing Next . If the
wrong overload class was selected, press Back and select
the correct class.
External By-Pass contactor (Ext ByPass)
If an External Bypass contactor is used, set the parameter to
Yes , otherwise select No .
Press Store to save the data.
Confirm the selection of external by-pass by pressing Next .
If the wrong selection was made, press Back and correct the
selection.
Tune Set
The configuration of the application setting menu is now
complete. If no tuning of the settings is desired, it is possible
to return to the top level by pressing Yes .
If tuning some parameters is desired, select Tune Set .