Chapter 10 - Functions
10:8 Kick Start
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Start
In some applications it may be necessary to kick loose the motor i.e.
initial friction, and therefore a kick start can be used. With this
function, a selectable fixed voltage is applied during a settable time.
Parameter
text
Kick Start
10:9 Kick Start Level
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Level
With this parameter it is possible to set the level of the kick start. It
is active only if kick start is selected.
Parameter
text
Kick Level
10:10 Kick Start Time
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Time
This parameter makes it possible to set the time of the kick start. It
is active only if kick start is selected.
Parameter
text
Kick Time
Default
Setting
value
range
No
Yes, No
Default
Setting
value
range
50%
50... 100%
Default
Setting
value
range
0.2 s
0.1... 1.5 s
Description
Selection of
Kick Start
Description
Level of Kick
Start
Description
Time for Kick
Start