Chapter 10 - Functions
This chapter describes all possible settings and functions in the softstarter, as
well as the easiest way of finding them. The respective default values, setting
ranges and parameter texts shown in the display are also described.
10:1 Setting Current
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Setting Ie
The setting of this parameter shall be according to the current the softstarter is
exposed to. If the motor is connected In Line, set the rated motor current (see
rating plate on the motor).
If the motor is connected Inside Delta, set the current in the Delta circuit by
multiplying the rated motor current by
Parameter
text
Setting Ie
Default
Setting
value
range
9...1380A
divided into
Individual
19
(size related)
overlapping
ranges
= 58% (or .58).
1/( 3)
Description
Rated motor
current
119