Chapter 7 - Settings and configuration
Second programmable input (In1)
Select the required function for the input In1.
One of the following functions can be selected:
None
No specific function (not activated).
Reset
Reset of a fault or overload condition.
Enable
When the In1=0 the softstarter stops immediately.
When In1=1 the softstarter is in normal operation.
Overrides all other inputs.
Jog
Performs a start ramp until command is released.
The motor stops immediately when the input
opens.
DOL
Open/close the bypass contactor
(PSTB370...PSTB1050).
Start3
Start signal for 3rd parameter set-up.
Press Store to save/activate the selected function.
85