Chapter 7 - Settings and configuration

7:2.4.8 Sequence start

Start / Stop
Protections
Warnings
Faults
Inputs
Outputs
Fieldbus
Seq. Start
The sequence start function can be used for starting several
motors or multiple speed motors with different parameter
sets such as individual ramp times, initial voltages, current
limits etc.
Up to three individual parameter sets can be used simulta-
neously.
The LOCAL CONTROL menu can not be entered if Se-
quence start is selected.
Number of sequences (No of Seq)
To set parameters related to a sequence start, enter the Seq
Start group.
Select the required number of parameter sets for the appli-
cation.
The following selections are available:
No
Sequence start is not activated.
The softstarter is in normal operation.
2
Two different parameter sets will be used.
3
Three different parameter sets will be used.
Press Store to save/activate the selected function.
First sequence setting current (1st Set Ie)
Set the current for the first parameter group and press Store
to save the value.
This parameter will only be displayed if parameter
No of Seq is set to 2 or 3.
Second sequence setting current (2nd Set Ie)
Set the current for the second parameter group.
Press Store to save the value.
This parameter will only be displayed if parameter
No of Seq is set to 2 or 3.