Detailed Explanation Of Setting Data - Mitsubishi Electric FX3G SERIES Programming Manual

Programmable controllers
Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
34.1.1

Detailed explanation of setting data

Details on the setting data in the FLCRT instruction are as shown below.
Setting items
S
1
S
2
S
3
+1
S
3
+2
S
3
+3
S
3
n
*1.
Adjust the maximum number of lines to specify the file size available in the used application software used.
Cautions
• When the file ID is "K0"
1) The CF-ADP can create up to 1000 files (within the CompactFlash
2) The file name is set to "FILE0000.CSV" to "FILE0999.CSV".
• When the file ID is "K1" to "K63"
1) The user can create up to 63 files (within the CompactFlash
2) The FLCRT instruction is completed abnormally if different file names are specified for the same file ID or if the
same file name is specified for different file IDs.
• It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"IVCK (FNC270) to IVMC (FNC275)" instruction and an
"FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.
742
File ID
This ID number is associated with the file name.
The FLCRT instruction creates a file, and associates the file name with the file ID at the same
time. The user should use the file ID for specifying a file after that.
Allowable setting range : K0 to K63 ("K0" indicates "FIFO file".)
File name
When
is "K0 (FIFO file)"
S
1
Not used (ignored)
Use an unused device. (D or R)
When
is "K1" to "K63"
S
1
Specify the file name in up to 8 characters until "null" or "null + null".
Half-width alphanumeric characters and half-width symbols permitted in the MS-DOS are
available.
Half-width symbols : !, #, $, %, &, ', (, ), +, -, @, ^, _, ', [, ], ~
The extension is fixed to "CSV"
Time stamp setting
Set whether or not the time stamp is added to the file. Specify the format when adding the time
stamp.
K0 : None (NULL)
K1 : yyyy/mm/dd hh:mm:ss
K2 : yy/mm/dd hh:mm:ss
K3 : dd/mm/yyyy hh:mm:ss
K4 : dd/mm/yy hh:mm:ss
K5 : mm/dd/yyyy hh:mm:ss
K6 : mm/dd/yy hh:mm:ss
K7 : hh:mm:ss
Data type
Set the data type to be saved.
K0 : No data type specification (mixed type)
K1 : Bit type
K2 : Decimal type (16-bit)
K3 : Decimal type (32-bit)
K4 : Hexadecimal type (16-bit)
K5 : Hexadecimal type (32-bit)
K6 : Real numbers (Floating point data) Exponent expression type
K7 : Character string
Maximum number of lines
Set the maximum number of lines.
Allowable setting range : K1 to K32767
When
is "K0"
S
1
TM
Set the CompactFlash
card use ratio.
Specify the ratio (%) out of the whole CompactFlash
Allowable setting range : 10 to 90 (%)
When
is "K1" to "K63"
S
1
File processing to be executed when the specified maximum number of lines is reached.
Set the file processing method to be executed when the number of lines reaches the specified
maximum value.
K0 : Stops execution. (The line position remains the specified maximum line position.)
K1 : Returns to the head (ring buffer file).
Channel number used by the CF-ADP
K1 : ch1
K2 : ch2
34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305
34.1 FNC 300 – FLCRT / File create
Description
*1
TM
card capacity to be used.
TM
card capacity).
TM
card capacity).
check
Data Type
16-bit binary
Character string
16-bit binary
16-bit binary
16-bit binary
16-bit binary
16-bit binary
16-bit binary

Advertisement