37. Operation of Special Devices (M8000 -, D8000 -)

37.1

Special Device List (M8000 -, D8000 -)

The device numbers and functions of the special auxiliary relays (indicated as "special M" in tables) and special data
registers (indicated as "special D" in tables) are shown below.
Note that functions of certain devices vary depending on the series of the PLC.
Do not use the undefined / blank special auxiliary relays and special data registers in the sequence program since
they are occupied by the CPU.
In addition, do not activate or write to the devices with brackets on the first letter such as [M]8000 or [D]8001 in the
program.
37.1.1

Special Auxiliary Relay (M8000 to M8511)

Number and name
PLC Status
[M]8000
RUN monitor
NO contact
[M]8001
RUN monitor
NC contact
[M]8002
Initial pulse
NO contact
[M]8003
Initial pulse
NC contact
FX
ON when either M8060, M8061, M8064, M8065,
[M]8004
M8066, or M8067 is ON.
Error occurrence
FX
ON when either M8060, M8061, M8063, M8064,
M8065, M8066, or M8067 is ON.
ON when battery voltage is below the value set in
[M]8005
D8006.
Battery voltage low
[M]8006
It is set when battery voltage low is detected.
Battery error latch
ON for 1 scan, when momentary power failure is
detected
[M]8007
Even if M8007 turns ON, PLC continues to RUN as long
Momentary power
as the duration of power loss is within the time period
failure
specified in D8008.
It is set when momentary power failure is detected.
[M]8008
If power loss time is longer than the time period
Power failure
specified in D8008, M8008 is reset and PLC is switched
detected
to STOP mode.(M8000=OFF).
[M]8009
ON when 24V DC power fails in either powered
24V DC down
extension unit or extension power supply unit.
822
→ Refer to Section 37.2 for supplementary information on analog special adapter devices.
Operation and function
RUN
input
M8061
Error occurrence
M8000
M8001
M8002
M8003
1 scan time
→Refer to Subsection 37.2.1.
, FX
, FX
3G
3U
3UC
,FX
,FX
,FX
,FX
1S
1N
2N
1NC
2NC
→Refer to Subsection 37.2.3.
→Refer to Subsection 37.2.3.
→Refer to Subsection 37.2.4.
→Refer to Subsection 37.2.4.
37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
Applicable model
Correspond-
FX
FX
FX
ing special
3G
3U
3UC
device
D8004
D8005
D8006
D8007
D8008
D8008
D8009
FX
FX
FX
FX
FX
1S
1N
2N
1NC
2NC