Fnc 50 - Ref / Refresh - Mitsubishi Electric FX3G SERIES Programming Manual

Programmable controllers
Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
13.1
FNC 50 – REF / Refresh
Outline
This instruction immediately outputs the latest input (X) information or the current output (Y) operation result in the
middle of a sequence program.
1. Instruction format
FNC 50
REF
P
2. Set data
Operand Type
D
n
3. Applicable devices
Bit Devices
Oper-
and
System User
Type
X
Y
M T C S D .b KnX KnY KnM KnS T C D R U \G
1
2
D
n
1: X000, X010 or X020:
2: Y000, Y010 or Y020:
3: FX
/FX
PLCs:
3U
3UC
FX
PLC:
3G
Mnemonic
16-bit Instruction
REF
5 steps
REFP
Head bit device (X or Y) number to be refreshed
Number of bit devices to be refreshed
(FX
/FX
: multiple of 8 ranging from 8 to 256,
3U
3UC
FX
: multiple of 8 ranging from 8 to 128)
3G
Digit Specification
Up to the final input number (whose least significant digit number is "0")
Up to the final output number (whose least significant digit number is "0")
K8 (H8) or K16 (H10): Up to K256 (H100) (which is a multiple of 8)
K8 (H8) or K16 (H10): Up to K128 (H80) (which is a multiple of 8)
13 High-Speed Processing – FNC 50 to FNC 59
Operation Condition
32-bit Instruction
Continuous
Operation
Pulse (Single)
Operation
Description
Word Devices
Special
System User
Index
Unit
V Z Modify
13.1 FNC 50 – REF / Refresh
Mnemonic
Operation Condition
Data Type
Bit
16-bit binary
Others
Real
Charac-
Constant
Pointer
Number
ter String
K
H
E
" "
P
3
3
339
11
12
13
14
15
16
17
18
19
20

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3u seriesFx3uc series

Table of Contents