Output driving method
It is required to include a LD or LDI instruction before the last OUT instruction in a state relay.
Change such a circuit as shown below.
X005
X005
State relay transfer method
Each OUT and SET instruction in state relays automatically resets the transfer source, and has the self-holding
function.
OUT instructions can only be used for transfer to a separate state relay in an SFC program.
Transfer
condition
Replacing "
" and " "
Replace the symbol "
flow with the OUT instruction.
Replace the symbol " " (used to express reset of a state relay) with the RST instruction.
<SFC program>
X001
40
X002
1
41
X004
2
41
790
STL
S20
Y001
Y002
Y003
Change
STL
S20
Y001
Y003
Y002
Move the
position.
STL
S41
Transfer to the next state relay
SET
S42
(SET instruction)
Transfer to a separate state
S50
relay (OUT instruction)
" used in SFC programs to express repeat, jump or transfer to a state relay in another separate
Y001
X003
3
TRAN
52
TRAN
Change
or
X005
M8000
RUN
monitor
<Step ladder>
X001
X002
TRAN
X003
X004
35 SFC Program and Step Ladder
35.2 Step Ladder
STL
S20
Y001
Y002
Y003
Insert "Always ON"
contact.
STL
S40
Y001
SET
S41
Replacement of "
S52
in the part 52
STL
S41
Replacement of "
RST
S41
in the part 41
"
"