Detailed Explanation Of Setting Data - Mitsubishi Electric MELSEC FX3U Programming Manual

Melsec fx series programmable logic controllers
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition

34.1.1 Detailed explanation of setting data

Details of the setting data in the FLCRT instruction are as shown below.
Setting items
S
1
S
2
S
3
+1
S
3
+2
S
3
+3
S
3
n
*1.
Adjust the maximum number of lines to specify the file size available in the used application software
used.
788
File ID
This ID number is associated with the file name.
The FLCRT instruction creates a file, and associates the file name with the file ID at
the same time. The user should use the file ID for specifying a file after that.
Allowable setting range : K0 to K63 ("K0" indicates "FIFO file".)
File name
When
is "K0 (FIFO file)"
S
1
Not used (ignored)
Use an unused device. (D or R)
When
is "K1" to "K63"
S
1
Specify the file name in up to 8 characters until "null" or "null + null".
Half-width alphanumeric characters and half-width symbols permitted in the MS-DOS
are available.
Half-width symbols : !, #, $, %, &, ', (, ), +, -, @, ^, _, ', [, ], ~
The extension is fixed to "CSV"
Time stamp setting
Set whether or not the time stamp is added to the file. Specify the format when adding
the time stamp.
K0 : None (NULL)
K1 : yyyy/mm/dd hh:mm:ss
K2 : yy/mm/dd hh:mm:ss
K3 : dd/mm/yyyy hh:mm:ss
K4 : dd/mm/yy hh:mm:ss
K5 : mm/dd/yyyy hh:mm:ss
K6 : mm/dd/yy hh:mm:ss
K7 : hh:mm:ss
Data type
Set the data type to be saved.
K0 : No data type specification (mixed type)
K1 : Bit type
K2 : Decimal type (16-bit)
K3 : Decimal type (32-bit)
K4 : Hexadecimal type (16-bit)
K5 : Hexadecimal type (32-bit)
K6 : Real numbers (Floating point data) Exponent expression type
K7 : Character string
Maximum number of lines
Set the maximum number of lines.
Allowable setting range : K1 to K32767
When
is "K0"
S
1
TM
Set the CompactFlash
card use ratio.
Specify the ratio (%) out of the whole CompactFlash
Allowable setting range : 10 to 90 (%)
When
is "K1" to "K63"
S
1
File processing to be executed when the specified maximum number of lines is
reached.
Set the file processing method to be executed when the number of lines reaches the
specified maximum value.
K0 : Stops execution. (The line position remains the specified maximum line position.)
K1 : Returns to the head (ring buffer file).
Channel number used by the CF-ADP
K1 : ch1
K2 : ch2
34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305
34.1 FNC 300 – FLCRT / File create²check
Description
*1
TM
card capacity to be used.
Data Type
16-bit binary
Character
string
16-bit binary
16-bit binary
16-bit binary
16-bit binary
16-bit binary
16-bit binary

Advertisement