1. When using (continuous operation type) ALT instruction
• When ALT instruction is used, a specified bit device is alternated in every operation cycle.
To alternate a specified device by turning the command ON or OFF, use the (pulse operation type) ALTP
instruction, or use a pulse operation type command contact such as LDP.
Program examples
1. Start and stop by one input
1)
When the pushbutton switch X000 is pressed, the start output Y001 is set to ON.
2)
When the pushbutton switch X000 is pressed again, the stop output Y000 is set to ON.
X000
M 0
M 0
2. Flicker operation
1)
When the input X006 is set to ON, the contact of the timer T2 turns ON instantaneously every 5 seconds.
2)
Every time the contact of T2 turns ON, the output Y007 is set to ON or OFF alternately.
X006
T2
X006
T2
3. Alternating output operation using auxiliary relays (M) (operation equivalent to ALT instruction)
The circuit below is provided as an example of alternating operation using basic instructions and auxiliary relays (M)
which is equivalent to ALT instruction.
1)
When X000 is set to ON, M0 turns ON and remains ON for only one operation cycle.
2)
When M0 turns ON for the first time, Y000 is latched. When M0 turns ON the second time, Y000 becomes
unlatched.
X000
M 1
X000
M 0
Y000
M 0
Y000
412
FNC 66
M 0
ALTP
Stop
Y000
Y001
Start
K50
T 2
FNC 66
Y007
ALT
M 0
M 1
Y000
14 Handy Instruction – FNC 60 to FNC 69
X006
5s
5s
5s
T 2
ON
Y007
14.7 FNC 66 – ALT / Alternate State
ON
5s
5s
5s
5s
ON
ON