Mitsubishi Electric FX3G SERIES Programming Manual page 354

Programmable controllers
Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
2)
FX
PLCs
3G
When the HSCS instruction is used in FX
Refer to the counting operation described below, and select according to the contents of control whether to use
the HSCS instruction or a general-purpose comparison instruction.
a) Case to select the HSCS instruction
-
When the output should be given if the counting result becomes equivalent to the comparison value
regardless of the scan time of the PLC
b) Cases to select a general-purpose comparison instruction
-
When counting is regarded as important, but the effect of the scan time can be ignored in operations
according to the counting result
-
When an instruction is used 6 times or more
FNC229
LDD<=
2. Device specification range
Only high-speed counters (C235 to C255) can be specified as
3. Only 32-bit operation instructions are available.
Because instructions for high-speed counters are dedicated to 32 bits, make sure to input "DHSCS (FNC 53)".
4. Priority order in operation among HSCS (FNC 53), HSCR (FNC 54), and HSZ (FNC 55)
instructions for the same high-speed counter
→ For details, refer to "6. Priority order in operations among HSCS (FNC 53), HSCR (FNC 54), and HSZ (FNC
5. Reset operation by an external terminal
6. For other cautions on using HSCS instruction, refer to the description later.
Program example
With regard to the current value of a counter, different outputs (Y) are arbitrary set to ON by two values.
M8000
RUN monitor
C255
0
Y010
Y011
352
K100
C251
55) instructions for the same high-speed counter" in Subsection 13.4.1.
→ For details, refer to "5. Reset operation by an external terminal" in Subsection 13.4.1.
K2,147,483,647
C255
S
S
1
2
FNC 53
K100
C255
DHSCS
S
S
1
2
FNC 53
K150
C255
DHSCS
Comparison
Comparison
value
source
150
... 149
101
100
... 99
13 High-Speed Processing – FNC 50 to FNC 59
13.4 FNC 53 – HSCS / High-Speed Counter Set
PLCs, the total frequency of each counter is affected.
3G
SET
Y010
FNC 50
Y010
K8
REF
S
.
Set the maximum counting value of
high-speed counter.
D
C255 = K100 → Y010 = ON
Y010
D
C255 = K150 → Y011 = ON
Y011
Output
destination
151
→ For details, refer to the next page.