Mitsubishi Electric FX3G SERIES Programming Manual page 794

Programmable controllers
Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
2. Example of selective recombination
Do not use MPS, MRD, MPP, ANB and ORB instructions in a transfer processing program with branches and
recombination.
Even in a load driving circuit, MPS instructions cannot be used immediately after STL instructions.
Pay attention to the programming order so that a branch line does not cross a recombination line.
<SFC program>
29
X010
1
50
<Step ladder>
STL
STL
STL
STL
X010
SET
STL
X011
SET
STL
X012
SET
Before recombination, first program the drive processing of state relays.
After that, program only the transfer processing to recombination state relays.
This rule should be observed to enable inverse conversion into an SFC program.
3. Example of parallel branch
Do not use MPS, MRD, MPP, ANB and ORB instructions in a program with branches and recombination.
Even in a load driving circuit, MPS instructions cannot be used immediately after STL instructions.
In the same way as programs for general state relays, program the drive processing first, and then program the
transfer processing.
Continuously program all transfer processing.
<SFC program>
20
X000
1
21
792
39
Y010
X011
TRAN
2
S29
Y010
S39
Drive
processing
Y011
S49
Y012
S29
S50
S39
Transfer
processing
S50
S49
S50
<Step ladder>
Y000
TRAN
31
41
49
Y011
X012
TRAN
3
<List program>
STL
S29
OUT
Y010
STL
S39
OUT
Y011
STL
S49
OUT
Y012
STL
S29
LD
X010
SET
S50
STL
S39
LD
X011
SET
S50
STL
S49
LD
X012
SET
S50
STL
S20
Y001
X000
SET
S21
SET
S31
SET
S41
35 SFC Program and Step Ladder
35.2 Step Ladder
Y012
TRAN
<List program>
STL
OUT
Drive
LD
processing
SET
SET
SET
Transfer
processing
S20
Y000
X000
S21
S31
S41

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3u seriesFx3uc series

Table of Contents