Integral controller
Table of Contents

Advertisement

(FISHER")
configuratron
5-39
5.8.6.1
5.8.7
Function
FCODE
Option
NO Default
Selected
Vallle
V&B?
Output
115
Disabled
0
0
Signal
Feedforward
enabled,
Al3
1
Processing
Feedforward
enabled,
A14
2
Tracking.
Output
DI (Al4)
3
Tracking,
Signal Selector
(Al4)
4
Min selection
enabled
5
Max selection
enabled
6
Output Signal Display
The displayed
output
signal may be reversed
(i.e. O-100%
actually
displayed
as 1000%).
This may be useful when the operator
is
familiar
with an increase
to close situation
(reverse
acting)
and the
displays
associated
with such a loop. Use FCODE
134 to select the
values displayed
as 0-i
00% or 10&O%.
Reversing
the output signal display
affects only the
display.
The up and down arrow keys and all other
control functions
remain
unchanged.
Function
FCODE
Option
No
Default
Selected
Value
Value
Output
134
O-l
00%
1
1
Signal
100-o%
2
Display
External Setpoint Output (A02)
The user may configure
the controller
to send the active setpoint
value, whether
remote,
local or computer
controlled,
out on analog
output 2 (A02)
using FCODE
114. Option
2 refers to the actual active
setpoint
value of the control
loop. Option
3 always refers to the local
setpoint
value regardless
of the configuration.
The remote
setpoint
at
Al2 can also be retransmitted
to A02 after signal processing
(i.e.
filtering,
square-root
extraction,
and arithmetic
handling).
Change
2 -July
1992
uM6.1:DPFf900:9147