Fisher DPR900 User Manual page 28

Integral controller
Table of Contents

Advertisement

Jumper
9 is used to terminate
the last controller
on the RS-485
communication
link. When the link is used, this jumper
must be cut on
all but the last controller
on the link. Otherwise,
it should
remain
intact.
2.6
Low-Level
Temperature
Input
A DPRlOO
Series Temperature
Input Module
may be plugged
into the
controller
to allow direct connection
of a low-level
input signal.
The
controller
internally
connects
this input to All. This disables
All for
other uses. For further
information
on the DPRlOO,
refer to Fisher
Controls
Bulletin
6.1 :DPRlOO.
The figure illustrates
the wiring of the
temperature
input module.
Signal
Ground
Notes:
D
When
a temperature
input nwdule
is connected
to All,
jumper
1 must be cut, and Jumper
5 must be intact.
A
floating
ground
(zero)
is n md.
DPR90M06
FCODE
119
must
be set to Option
2 (O-20 mA,
O-5 V) if a DPRlOO
Series Temperature
Input
Module
is used.
UM6.l:DPR900:9102
May 1991