Change
tuning
parameters
according
to the following
procedure:
Step
Button
Display
Action
1
w
0
PROG
Select program
mode;
PROG
button
LED starts flashing.
PROG
or
If an error code is present
(e.g. E107), it appears
in the digital
El07
display.
Call up any additional
error codes by pressing
either
green increase
or decrease
buttons.
@@
Leave the error code mode without
clearing
the error by
pressing,
D
0
PROG
or
Press
TUNE
button to erase the error codes.
2
Q
0
FC 1
TUNE
*
4
v
0
50.50
TUNE
f!P
6
u
0
FC n
R
Authorization
check is configured.
The configured
values
may only be viewed,
not changed
(Steps 2 and 3). Steps 4
and 5 change
values
only when authorization
check is not
configured.
Step forward (using the green increase
button)
or backward
(using the green decrease
button)
to the desired
function
code. The
SET
button flashes.
Push the
SET
button to view the current
parameter
value for
the selected
function
code.
Using the green increase
and decrease
buttons,
set the new
value in the digital display.
The
STORE
button starts to flash,
indicating
that the changed
value must be stored to take
effect.
Press the
STORE
button to store the new value; the PROG
button starts to flash, and the digital display
shows the next
function
code.
Call other function
codes
by using the green increase/decrease
buttons,
then complete
Steps 3 thru
6 to change
the parameters.
v
0
27.3
7
Press the flashing
PROG
button;
the controller
leaves the
PROG
programming
mode, and the display
shows the configured
display value.