2.7
Notes:
D
Chassis ground
D
For voltage inputs the resistance
jumper must be cut.
Analog
Input Signals
Connect
analog
inputs All thru Al4 to the appropriate
terminals
on
the back of the mounting
cassette.
Some
examples
of connections
are shown in the figure. Select the Al signal ranges
(O-20 mN4-20
mA or O-5 V/l -5 V) during
configuration
as explained
in Section
5.
Ensure that shields are connected
to chassis
ground
by using either
of the two lugs at the upper edge of the rear panel.
If a Pt-100
sensor or thermocouple
is used without
a transmitter,
it
must be connected
directly
to a DPRIOO
Temperature
Input Module
mounted
on the module
block. This disables
the use of All for any
other signal.
D
For voltage Inputs the
resistance
jumper
must be cut.
The DPRSOO accepts
signals
from field-powered
transmitters
and
can supply the required
24 Vdc to most remotely-powered
transmitters.
The figures
show how to connect
external
sensors
powered
either by the controller
or by an external
source.
The
terminal
block connector
numbers
for All are shown,
although
the
connection
information
applies
to all analog
inputs.
May 1991
UM6.1:DPR900:9102