(FE+
Configuration
5-5
When supplying
a voltage
signal on any of the
analog
input signal terminals,
ensure
that the
appropriate
jumper
is cut at the back of the
mounting
cassette.
Cutting
the jumper
disconnects
the 250 ohm shunt resistor.
Use FCODE
143, to display any of the analog
inputs other than the
default
(process
value, input signal All).
When the default
value is
used in conjunction
with FCODE
106, the value indicated
is in
resealed
units.
Function
FCODE
Option
No
Default
Selected
VallJe
Vhle
Normal
143
Display process value
1
1
Display
Display All, in percent
2
Display Al!?, in percent
3
Display Al3, in percent
4
Display Al4, in percent
5
Perwltage
Value
The other display
options
show the analog
input values
as a
percentage,
after filtering
(if selected)
and linearization
(if selected).
When the display
shows an analog
input other than the process
ra
value.
value, the input signal number
appears
to the left of the percentage
Analog
Input Number
The user may configure
input signals
Al3 or Al4 as reference
signals
DPR90~024 for the gain scheduling
function.
When
one of these inputs is used
as a reference
signal, the user may wish to configure
the selected
reference
signal to appear
on the digital
display
by setting
the value
of FCODE
143 to option 4 or 5.
5.4.2
Analog Inputs Using DPRIOO Series
Temperature
Input Module
The DPRSOO
accepts
either a 4-20
or O-20 mA signal from a
temperature
transmitter,
direct RTD or thermocouple
temperature-sensor
input via a DPRIOO
Temperature
Input Module.
Any temperature
module
connected
to the controller
sends
its input
signal via the All terminals,
disabling
All for any other input.
When a temperature
input module
is present,
ensure
that Jumper
1 is
cut and Jumper
5 is intact. Set FCODE
119 to Option
2 (Al 1 signal
range G20
mA). Also select the appropriate
option for FCODE
118.
May 1997