Setpoint Ramp And Hold - Fisher DPR900 User Manual

Integral controller
Table of Contents

Advertisement

[FsnEk;]
Configuration
5-33
5.7.8
Setpoint
Ramp and Hold
May 1991
Changing
the SP limits also changes
the O-100
percent
scales
used by the SP and PV bargraphs
to that of the setpoint
limits: 0 percent
= lower limit
and 100 percent
= upper limit.
When setpoint
limiting
is used, and the user elects
to retransmit
the SP signal out on A02,
the
transmitted
signal will be the resealed
O-l 00%
signal.
Setpoint
ramping
may be required
for slow starting
systems,
such as
a steam system
that requires
warming
up. The user selects
initial
setpoint
ramping
options
via FCODE
109. The controller
may ramp
either the remote
or the local setpoint
value and can be configured
to
indicate
Ramp Status
with DO3 and D04.
Function
FCODE
Option
No
Default
Selected
VZllW
V&e
Setpoint
109
Disabled
0
0
Ramping
Enabled,
output on
DO>DO4
1
Enabled,
no indicated
output
2
When ramping
is configured,
the ramp speed and ramping
time period
must be set via FCODE
13 and 14.
Function
Paramefers
Setpoint
Ramping
rate
Ramping
Ramping
timer
FCODE
Range
Unit
Increment
Default
Selected
Vak
V&.K3
13
Mt?k?S.
Min.
1 digit
Max
14
O-999
Min.
1 digit
1 Min
The controller
determines
the ramp direction
(up or down) depending
on whether
the setpoint
value lies above or below the current
process
value. The ramp starts when the controller
is switched
from manual
to
auto. This switching
can be manual
or done via the control
signal at
Dll or Dl2.
The following
shows an example
of the controller
ramping
function.
UM6.1 :DPf?900:9102

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents