Fisher DPR900 User Manual page 41

Integral controller
Table of Contents

Advertisement

Controls
and
lnd;cators
3-5
3.3
3.3.1
100
90
60
70
60
50
40
30
20
10
n
PV % SP
Bargraph
Displays
Process Values
The process
value bargraph
displays
the process
value or any
deviation
alarm
limits which may have been set. The two types of
alarm limits are high/low
and deviation
alarms.
Only one type may be
present
at a time.
High/low
alarms
are indicated
by a brighter
bar for each alarm
setting.
A maximum
of two alarm points may be set. The upper and
lower bright bars indicate
the high-high
and low-low alarms.
If the
alarm
points are separated
by less than 2.5%, only one bar is
shown.
Deviation
alarms
are shown in the same manner
as high/low
alarms.
The alarm limits however,
are set relative to the setpoint
and change
when the setpoint
changes.
If the alarm
limits are separated
by less
than 2.5%, only one bar is shown.
The display
at the left indicates
a PV low setpoint
deviation
alarm of
25%. The display
at the right indicates
PV alarms
set at 82 and 50%.
Setpoint
The setpoint
bargraph
normally
displays
the setpoint
value. If the
point ramp is in operation,
the setpoint
final value is shown as a
brighter
bar during the ramp operation
period.
In the display
shown, the final operator
set ramped
setpoint
is 87%,
while the current
setpoint
is 75%.
Output Signal
The reading
of the output signal display
is dependent
on the mode of
operation
selected.
May
1991
lJM6.1:DPR900:9102