Fisher DPR900 User Manual page 67

Integral controller
Table of Contents

Advertisement

[FISHER")
Configuration
5-13
Function
FCODE
Option
133
Not connected
Conneded
to A14
Connected
to Al3
No.
Default
Selected
V&F?
V&e
1
1
2
3
Fisher Controls
recommends
the use of actuator
feedback
whenever
possible.
If no actuator
feedback
potentiometer
is used, the user must
short A01 on the connection
terminal
block. This
will prevent
an open-circuit
alarm (Err 4) from
being generated.
If required,
the controller
can be configured
to supply
the feedback
potentiometer
with current
from A01 (when not used for other
purposes).
Use FCODE
29 to select the current
supplied
to the
potentiometer.
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
Value
Vallle
Potentiometer
Current
output
29
c-20
mA
0.1 mA
5mA
Feedback
The potentiometer
signal received
at Al4 can be amplified
by using
FCODE
30 The selected
current multiplied
by the potentiometer
resistance
must result in a voltage
drop of 5V (i.e. the feedback
signal
from the potentiometer
must be 0-5V for l-100%
actuator
positioning.
Use FCODE
31 to set a zero-level
offset for the potentiometer.
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
Value
Value
Actuator
Gain
30
O-9.99
-
0.01
1
Feedback
Zero offset
31
+100
%
1%
0
Signal
Change
1 -September
1991
UM6.1:DPR900:9102