2.12
1
sensor
PT I Potential
t
f Groundino
Ponnihilitv
1
-1ov
Not permitted,
Max CMV is -5 V
2
-5 v
Permitted
3
ov
Permitted
4
+38
V
Not permitted,
Max CMV is +24 V
The figure depicts
a current
loop example
for a DPRSOO controller.
In this example,
it is assumed
that all units are isolated
from the
main power supply
ground.
This type of current
loop must always be
grounded
at a single point so that a floating
ground
does not occur
and introduce
a large interference
potential.
Installing
the Mounting
Cassette
To fit the mounting
cassette
into the panel cutout:
q
Position
the mounting
cassette
(without
the controller
inserted)
in the panel cutout as shown.
q
Position
the lower retaining
spring
as shown.
Hold the
mounting
cassette
in place with the thumb
and use the index
finger to press the spring down.
o
Insert the upper retaining
spring,
as shown on the next page,
to complete
the installation.
Change
2 -July
1992
uM6.1:DPR900:9147