Configuration
5-21
5.6.3.3
Deviation
Alarm
Limits
The DPRSOO
is capable
of externally
indicating
setpoint
deviation
alarms,
provided
that absolute
alarms
have not been selected.
Configure
setpoint
deviation
alarms
using FCODE
104. The controller
measures
deviation
and activates
deviation
alarms for the process
value relative
to the current
setpoint
value as shown in the figure.
These
alarms
have a hysteresis
of 1 percent
of the configured
range.
1
Function
FCODE
Option
NO Default
Selected
Value
Value
Deviation
104
Disabled
0
0
Alarm
Enabled
1
Selection
-
Positive -
DO4 is activated
Deviation
DO4 is deactivated
and H flashes
and H stops flashing
PV alarms,
setpoint
deviation
alarms,
sensor
status,
and setpoint
ramping
all use DO3 and DO4
and are mutually
exclusive.
If more than one of
these functions
is set at a time, the display flashes
ERROR.
Use FCODE
5 to set the setpoint
negative
deviation
limit in the range
0 to the lower measuring
range limit.
Use FCODE
6 to set the setpoint
positive
deviation
limit in the range 0
to the upper measuring
range limit.
Function
Parameters
Deviation
Negative
limit
Alarm
Positive limit
Limits
FCODE
Range
Unit
Increment
Default
Selected
Value
Value
5
W-W
a"Y
1 digit
-Ma
6
'W+M)
any
1 digit
+Max
Brightly
lit bars on the process
value bargraph
indicate
the setpoint
deviation
alarm
limits. The deviation
alarm limits interact
with the
setpoint
value and change
automatically
if the setpoint
value is
altered.
Change
2 -July
1992