Fisher DPR900 User Manual page 18

Integral controller
Table of Contents

Advertisement

l-6
Introduction
3OF (1.5OC) for 100 ohm Platinum
RTD
Scan Rate
All inputs and outputs
scanned
and updated
five times
per second
(200 ms)
POWER REQUIREMENTS
AC Power
11 O/120 or 220/240
Vat, + 10% at 50/60 Hz. Power
consumption
lOVA,I7VA
maximum.
DC Power
24 Vdc + IO%, 7.2W maximum,
excluding
I/O circuits
External
Load
24 Vdc + IO%, 100 mA total with ac supply.
Three-stage
pulse output
supplies
up to 20 mA to
potentiometer
(750 ohms).
ENVIRONMENTAL
REQUIREMENTS
Temperature
32 to 122OF (0 to 50°C) in operation.
Installation
Flush fitting in mounting
cassette,
installed
with
retaining
springs
from the front panel.
Environmental
Classification
In accordance
with IEC 529, IP20 in all directions
(meets
or exceeds
NEMA
12), IP65 from the front
when mounted
in a sealed
panel
Electrical
Connections
Screw terminals
will accommodate
up to 14 AWG
(1.5mm2)
wire. All connections
located
in terminal
blocks on the rear of the mounting
cassette.
Computer
Communications
Standard
RS-485
serial interface
(COMLI
protocol)
UM67:DPR900:9102