Local Setpoint (Lsp); Extra Internal Setpoint (Esp) - Fisher DPR900 User Manual

Integral controller
Table of Contents

Advertisement

5-24
Configuration
[FISHER"]
1 - Local internal
setpoint
(LSP)
2 - Extra internal
setpoint
(ESP)
3 - Remote
setpoint
(RSP)
4 - Computer-controlled
setpoint
(CSP)
5 - Externally
controlled
via digital signals
(SPC)
The user configures
the setpoint
source the controller
uses via
FCODE
142.
Function
FCODE
Option
NO
Default
Selected
V&e
V&K?
Automatic
142
Disabled
1
1
Setpoint
Switches
to remote setpoint
2
Switching
Switches
to extra internal setpoint
3
When
option 2 is configured
and the R button is pressed,
the
controller
switches
to the RSP value.
When
option 3 is configured
and the R button is pressed,
the
controller
switches
to the ESP value.
When
external
remote
or local switching
capability
is configured,
an
external
discrete
signal connected
to either DII or D12 can remotely
activate
the switch. Remote
switching
is selected
via FCODE
111.
Function
FCODE
Option
No
Default
Selected
ValUe
Value
External
111
Disabled
0
0
WL
Remote/Local
switching
via Dll
1
Switching
Remote/Local
switching
via DIZ
2
When
remote
switching
via discrete
inputs is configured
and the
signal line is inactive,
the controller
switches
to LSP control.
When the
discrete
input returns to the opposite
state, the controller
reverts to
using the RSP value (assuming
the R button is still lit).
5.7.1
Local Setpoint
(LSP)
When
no setpoint
options
are configured,
the controller
accepts
a
local setpoint
(LSP) value,
entered
with the green increase/decrease
buttons.
Set the LSP value according
to the instructions
in Section
3,
Establishing
a Setpoint.
A local tracking
option
is available
for selection
when using LSP
control.
This option provides
automatic
setpoint
tracking
when the
controller
has been placed
in the manual
mode via the manual
button.
tJM61:DPR900:9102
May 1991