Fisher DPR900 User Manual page 27

Integral controller
Table of Contents

Advertisement

2.5
Route a 14 AWG (1.5 mm*)
conductor
from terminal
36 to the
instrumentation
system dc ground
point. Then run a 10 AWG (5.26
mm*)
multistrand
conductor
from the instrumentation
system
dc
ground
point to the existing
plant ground
grid. This point on the plant
ground
grid must be dedicated
exclusively
to the instrumentation
system
dc ground
and must not be used for other equipment
grounding.
Use crimped
or thermal-welded
connections
at all ground
points.
Jumper
Module
@
Caution
Ensure that power to the controller
is OFF,
prior to cutting
jumpers.
Leave
sufficient
metal to solder jumper
back together
if
required.
The jumpers
on the back of the mounting
cassette
determine
the
electrical
termination
characteristics
of the four analog
inputs and the
RS-485
communications
wiring. All of the analog
inputs, All thru Al4,
have 250 ohm input resistors.
There
is also a 100 ohm termination
resistor
on the RS-485
connection.
The figure shows the jumper
module
and the table describes
the connection
each jumper
makes.
input resistor Al2
Input resistor
A14
Floating
ground All
Floating
ground Al2
Floating
ground Al3
Floating
ground Al4
Current
In
Current
In
current
In
Current
In
Fixed GND
Fixed GND
Fixed GND
Fixed GND
YES
Voltage
In
Voltage
In
Voltage
In
Voltage
In
Floating
GND
Floaring
GND
Floating
GND
Floating
GND
NO
Jumpers
1 thru 4 connect
the 250 ohm input resistors
in series so
that the 4-20 mA input signal can be converted
to a I -5V signal inter-
nally. Cut the appropriate
jumper
to accept a direct
l-5V signal on
1...5...!3
the input terminals.
Jumpers
5 thru 8 connect
inputs All thru Al4 to
DPR90c-5% the controller
supply ground.
Cut the appropriate
jumper
to allow the
negative
input terminal
to float between
-5 V and 17 V, with respect
to supply ground.
May 1991
UM61:DPR900:9102

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents