Manual Output Signal Control (Aol); Output Signal Limiting (Aol); Forced Output Control (Aol) - Fisher DPR900 User Manual

Integral controller
Table of Contents

Advertisement

5-36
Configuration
@iiF==
5.8.1
5.8.2
5.8.3
c+ 4
Note
Manual
control
of output signals
is only possible
when the M button and the manual
mode
increase
/decrease
buttons
are active (yellow LED's lit).
When only the M button is lit, the controller
has
been forced to the manual
mode externally,
i.e.
with discrete
switching
signals
or through
the
RS-485
communications
link.
Manual Output Signal Control (AOI)
Press the M button to select the manual
mode. The yellow
LED's in
the M button
and the increase/decrease
buttons
light to indicate
Manual
mode.
The user can then change
the output signal in 0.5
percent
increments,
using the yellow increase/decrease
buttons.
To return to the Auto mode,
simply
press the M button again.
The
yellow LED goes out, indicating
Auto mode.
Output Signal Limiting (AOl)
To
prevent
output signals
on A01 from exceeding
specified
limits, set
upper and lower output signal limits,
using FCODE
7 and 8. Select
output signal limiting
using Fcode 105. Output
signal limiting
does not
apply to raise/lower
outputs.
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
Vallle
V&e
Output
Lower limit
7
0-i 00
%
0
Signal
Upper limit
8
O-100
%
Limits
Pl)
~,
Signal limits apply m Auto only
2
Forced Output Control (AOl)
With the exception
of the raise/lower
(positioning
motor) outputs,
the
controller's
output signal A01 may be forced to a preset value by a
discrete
input at Dll or Dl2.
Enable
or disable
the forced control function
via FCODE
112.
UM6. i:DPR900:9102
May 1991