5.14
Example
2 -
Flow Regulation
eegend
1 DPRSOO Controller
2 I/P convewr
3 Control Valve
4 Throttle
5 Shut-off Valve
6 Valve Block
7 Differential
Pressure
*ensor
In the following
figure the process
requirement
is for the normally
closed
valve to open if the control
pressure
fails. The valve also
closes
if the flow rate increased.
In either case an increasing
process
value yields an increasing
output signal from the controller,
The
controller
must be configured
for direct output.
Alarm
and Fault Indications
The controller
can monitor
the process
value or the deviation
between
the process
and setpoint
values
and internal
functions.
514.1
Fault Indication
There
are two types of fault indications,
based on the severity
of the
error. Error code values
less than 100 are controller
fatal faults that
effect the basic operation
of the controller.
These
errors are indicated
as Err n on the digital display
and DO3 and DO4 are simultaneously
activated.