Remote Setpoint (Rsp) - Fisher DPR900 User Manual

Integral controller
Table of Contents

Advertisement

Configuration
5-27
Remote Setpoint (RSP)
The DPRSOO can be configured
to receive
an externally
generated
signal and use it as a remote
setpoint
(RSP).
The controller
receives
the RSP value via analog
input Al2 and uses this, or the extra internal
setpoint,
as the setpoint
value when the user pressed
the R button.
The user may condition
the incoming
remote
signal using the
following
functions:
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
Vallle
Vallle
Ratio
Gain
1
o-9.99
0.01
1
(A1.3
J
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
V&e
V&e
Bias
Zero level offset
2
+ Meas.
="Y
1 digit
0
W)
Range
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
Value
ValUe
Filter Al2
Time constant
16
o-9999
s
IS
0
Function
FCODE
Option
NO Default
Selected
Value
V&X
Signal
120
4-ZOmA,
1%5V
1
1
Range
O-ZOmA, 0-5V
2
VW
4-ZOmA,
l-5V,
Square
root
3
C-ZOmA, C-5V. Square root
4
An arithmetic
expression
(or calculation),
can be selected
using
FCODE
108. The result is used as the RSP input. The values of
Ration
and Bias are determined
by FCODE
1 and 2.
I
I
Al2 -
FCODE 16
FCODE
120
Filter
Square
Root
FCODE
106
Arithmetic
-
RSP
A,3 _
FCODE 17
FCODE
121
Filter
-
Square
Root
DPR900~-034
May 1991
UM6. I:DPR900:9102