Fisher DPR900 User Manual page 22

Integral controller
Table of Contents

Advertisement

2.2
Controllers
cannot
be installed
vertically
in the
same cutout.
Cutouts
should
not be closer than
shown above.
Make the cutouts
in the panel according
to the dimensions
and
spacing
shown. For multiple
installations,
make the cutout wider
according
to the following
formula:
Cutout
width (W) = N x B - 0.19 inch (4.5 mm)
where:
N = number
of controllers
to be mounted
B = unit width = 2.84 inches
(72 mm)
Tolerance
= + 0.04 inch (1 mm) per unit
Wiring
the Mounting
Cassette
The DPRSOO
Integral
Controller
fits into a standard
panel-mount
cassette.
The mounting
cassette
has terminal
blocks on the rear for
all electrical
connections.
Connect
all wiring to the terminal
blocks
before inserting
the cassette
into the panel cutout
unless the rear of the cassette
will be accessible
after installation.
2.3
Power and Ground
Wiring
The power source for the DPRSOO Controller
should be free of
electrical
noise. Do not use sources
that supply power to relays,
contacts,
or thyristor-controlled
equipment.
If no other source
is
available,
use an isolation
transformer
or magnetic
voltage
stabilizer.
Do not connect
electrically
noisy equipment
and the DPRSOO to the
same secondary
of such a transformer.
Closely
follow the
manufacturer's
recommendations
concerning
the grounding
01 the
isolation
transformer.
When
operating
the controller
from an alternating
current
source,
always
use a 3-wire power cord. Connect
the neutral wire to terminal
41 and the ground wire to terminal
42 on the terminal
block. Connect
the supply
line wire to the appropriate
terminal
for the power being
The controller
operates
on either 50 or
lJM6.1:DPR900:9102
May 1991