Fisher DPR900 User Manual page 58

Integral controller
Table of Contents

Advertisement

5-4
Configuration
(FISHER;)
The measuring
range is set using FCODE
1 to 3.
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
V&Je
ValLJe
Measuring
Min value
24
+ 9999
any
1 digit
0.0
range
Max value
25
+ 9999
any
1 digit
100.0
No. of
26
O-4
1
1
5.4.1.5
The parameters
should be inserted
in the order
FCODE
26 thru 24 (number
of decimals
first) to
obtain the correct values.
Example:
A level controller
is to regulate
between
0.39 and 1.16 inches
(10 and
30 mm). The sensor supplies
0 mA for 0 inches (0 mm), and 20 mA
fpr 1.97 inches
(50 mm). Set FCODE
3 to 1, FCODE
1 to 0.0 and
FCODE
2 to 500.
Signal Range Selection
Use FCODE
119 thru 122 to select the appropriate
electrical
signal
range and linearization
option for each of the four analog
inputs, All
thru Al4. Select one of the options.
To enable the square
root option
for Al 1, use FCODE
107.
nction
FCODE
Option
No
Default
Selectel
Value
V&e
All
119
4-20mA.
1-W
1
1
O-20mA.
0-W
2
Al2
120
4-20mA,
1-W
1
1
O-20mA,
0-5V
2
4-2OmA,
1+X
square
root
3
&2OmA,
0%5V, square
root
4
Al3
121
4-20mA,
1-W
1
1
O-20mA,
0-W
2
4-ZOmA,
I-.5V, square
root
3
0-2OmA,
0-5V, square
root
4
Al4
122
4-20mA,
ILW
1
1
0%ZOmA, 0-W
2
4-20mA.
I-W,
square
root
3
0-20mA.
0-5V, square
root
4
Function
FCODE
Option
No
Default
Selected
Value
Value
Calculation
to7
Disabled
0
0
of Process
square
root
1
Variable
R = (All x Ratio) + Bias
2
R z All + (Al3 x Ratio) + Bias
3
R = (All x Ratio) + Al3 + Bias
4
R = (All x AI3)(Ratio)
+ Bias
5
UM6.1:DPR900:9102
May 1991