Tracking Signal Selector (Option 4) - Fisher DPR900 User Manual

Integral controller
Table of Contents

Advertisement

5-388
Configuration
(FISHER]
5.8.5.2
Tracking
Signal
Selector
(Option
4)
Option
4 should
be selected
when twp DPRSOO
controllers
are used
and the high (or low) analog
output signal between
the controllers
is
selected
for use with the final control
device
by the second
DPR
controller.
Option
4 is used only in the controller
supplying
its output signal to
another
DPR controller
and used with the second
controllers
Mm/Max
signal
selection
(FCODE
115, Option
5 or 6). Option
4 allows for
automatic
integral
output
tracking
between
the two controllers,
utilizing
the analog
input signal connected
at Al4. This signal must be
the output signal selected
for transmission
to the final control
device.
Function
FCODE
Option
No
Default
Selected
Value
Value
output
115
Disabled
0
0
Signal
Feedforward
enabled,
Al3
1
Processing
Feedforward
enabled,
Al4
2
Tracking,
Output DI (Al4)
3
Tracking.
Signal Selector
(Al4)
4
Min selection
enabled
5
Max selection
enabled
6
This output tracking
function
cannot be used with positioning
motor
(raise/lower)
outputs.
Function
FCODE
Option
NO
Default
Selected
Value
ValW
EXtlXflal
110
Disabled
0
0
A/M Track
AuWManualTTrackswitchingvia
Dll
1
Switching
AutoIManual~rack
switching
via Dl2 2
5.8.6
Output Min/Max Signal Selector (AOl)
The output min/max
function
lets the output
signal be controller
by
either Al4 or the controller-calculated
AU (delta U) value. AU is
calculated
as A01 + AU. AU is the contribution
from the controller
during
regulation
(max + 10%).
The minlmax
selection
is only active in the auto mode. Additionally,
the function
cannot be used in conjunction
with positioning
motor
(raise/lower)
pulse outputs.
UM6.1:DPR900:9102
Change
1 -September
1991