5-14
Configuration
[FISHER"]
5.5.1.3
Pulse Width
Modulated
Output
(Option
3)
This option provides
for discrete
output
of the PID signal in a
two-stage
pulse-width
modulated
format through
DO5
This output
should
be connected
through
an intermediate
relay or contactor.
If the
load is inductive,
a diode must be wired across the output.
An
increasing
control
signal forces DO5 to conduct
for a longer
percentage
of the specified
cycle time. At the maximum
output signal
(loo%),
the pulse width equals the selected
pulse cycle time and
results
in a continuous
ON signal.
The cycle time must be selected
in
relation
to the time constant
of the process
and should
be shorter than
five time-constants.
The minimum
resolution
is one controller
sampling
period
(0.2 seconds).
Use FCODE
32 to define the total cycle time.
+
LP
A0
1-
Cycle Time
Minimum
Pulse 0.2s
DO5
-
v+
Pulse Length
Increasing
Output Signal
DPR9Dce28
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
V&e
Valtie
Pulse-Width
Cycle time
32
l-999
s
1s
100
Output Option
When pulse-width
modulated
output is selected,
A01 must be shorted
on the connection
terminal
block (Pins 9 and 10).
5.52
Discrete
Outputs
The DPRSOO
Controller
provides
for the use of 24Vdc discrete
outputs
to be used for external
indication
of switching.
Select active state
definition
for DO14
using FCODE
129 thru 132. The controller
defines
a discrete
output signal as active when conducting
or open.
Change
7 -September
1991