Fisher DPR900 User Manual page 26

Integral controller
Table of Contents

Advertisement

2.4
oundmg
The 24 Vdc terminal
can supply a maximum
external
load of 100 mA when powered
from 110,
120,220
or 240 Vat power sources.
This supply
is
intended
to power transmitters
or relays connected
to the discrete
outputs.
The 100 mA limit applies
only to ac powered
units. No internal
load,
including
the two analog
outputs,
need be included
in the 100 mA total.
Controllers
powered
from 24 Vdc sources
have a
current
limit of 250 mA on each output.
To operate
the controller
from a 24 Vdc supply,
connect
the power
supply leads to 24 V terminals
35 and 36 (observe
the proper
polarity).
Signal
Wiring
Connect
all input and output wiring to the terminal
blocks at the rear
of the mounting
cassette.
Use direct runs of individually
shielded,
twisted-pair
wire in an insulating
jacket.
The maximum
wire size for
terminal
connectors
is 14 AWG (1 .5mm2).
The insulating
jacket
should only be stripped
to allow the length of wire required
to con-
nect the twisted-pair
to the terminals.
For long runs, it may be practical
to route field wiring to a junction
box, then through
multi-pair
shielded
cable. Lace wires as required
by local electrical
codes or plant standards.
Connect
the shield and
drain wires to the grounding
bus bar as shown. Standard
practice
is
for shields
to be grounded
at the signal source
only. If the shield is
grounded
at the DPR (vs the external
instrument),
also tie it to the
LGB. Shield
wires should not be stripped
further than one inch from
the end of the signal wires.
Route a 14 AWG (1.5 mm*)
conductor
from the mounting
cassette
ground
to the panel ground
point. Then use an AWG 8 (8.37 mm2)
multistrand
conductor
or 0.50 inch (12.7 mm2) braided
ground
conductor
(preferred)
to connect
the panel ground
point to the LGB.
The panel ground
point and the ground
of the ac power source for the
unit should be connected
to the same grounding
bus bar. This
minimizes
the possibility
of significant
voltage
between
ground
points.
Use crimped
or thermal-welded
connections
at all ground
points.
UM6.1:DPR900:9102
May 1991

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents