Comli - Fisher DPR900 User Manual

Integral controller
Table of Contents

Advertisement

[FISHER")
Configuration
5-43
FCODE
33 sets the maximum
running
time for the controller
to
change
the setpoint
from 0 to 100% (or 100 to 0%). Choose
options
from the following
FCODE's:
1 Function
1 Parameters
1 FCODE
1 Ranw
i Unit
1 Increment
1 Default
1 Selected
1
Value
V&e
DDC
Time for 0 to 100%
33
1-99s
s
1s
100s
Running
Time
Function
FCODE
Option
No
Default
Selected
ValUe
VailJe
EXtWlal
111
Disabled
0
0
WL
Remote/Local
switching
via Dll
1
Switching
Remote/Local
switching
via Dl2
2
5.9.3
COMLI
Function
FCODE
Option
NO Default
Selected
Wile
Value
Setpoint
141
Extra internal setpoint
1
1
Computer
External
remote setpoint
2
Control
Function
FCODE
Option
No
Default
Selected
Value
Value
Automatic
142
Disabled
1
1
Setpoint
Switches
to remote setpoint
2
Switching
Switches
to extra internal s&point
3
External
switching
to local mode via Dll and D12 is still possible
(switching
to remote
from local is not possible).
As in any data
communications
mode,
control
of the setpoint
value is only available
by activating
the R button,
otherwise
the controller
remains
in local
control
mode.
COMLI
is the communication
protocol
that defines
how information
held within the controller
resident
registers
can be sent to a computer.
This is called the RS-465
communications
link. A full description
of the
COMLI
protocol
and its application
in communicating
with the
DPRSOO
controller
are contained
in a separate
manual,
UM6.1:
DPR-COMLI,
available
from you Fisher Representative.
When the
user selects
Option
4 of FCODE
117, COMLI
communications,
they
must enter the COMLI
address
for the controller
in FCODE
46. No
two controller's
on the same link can have identical
addresses.
1 Function
lParameters
1 FCODE
IRan&
1 Unit
I Increment
I De&It
1%;~
I
I
I
I
I
COMLI
Controller's
46
l-255
1
ID
Highway
Address
May
1991