Confiouration
5-4 1
Start-Up
and Fatal Fault Values
Select
an output signal value for the controller
to use at startup
and
/or configure
the controller
to hold the current output signal level, or
go to a preset signal
level in case of a fatal fault during continuous
self-testing.
Use FCODE
20 to set the initial output signal start-up
value for A01 in
the range O-100 percent.
The value must be within the output signal
limits if any are configured.
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
V.he
ValUe
StXf
output
Signal
20
o-1 00
%
1%
0
Value
(A01 )
Use FCODE
113 to select the start value option the controller
uses
when it detects
a fatal controller
error.
Function
FCODE
Option
NO Default
Selected
Value
WW
COlltlOllf3
113
Freeze output,
at current level
1
1
Fault
set OutDut level to preset value
2
Use FCODE
21 to set the preset failure
output signal level for A01
in
the range O-100 percent
to be used in the event of a fatal controller
error as selected
with FCODE
113, Option
2.
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
Value
Value
Controller
Output signal (AOl)
21
o-100
%
1 %
0
Fault
These functions
are not applicable
for positioning
motor (raise/lower)
outputs.
5.9
Computer
Control
The following
covers controller
communications
with a supervisory
system
and external
control
of either the setpoint
or the output signal.
FCODE
117 determines
the data communications
configuration
of the
controller.
May 1991
UM6.l:DPR900:9102