Tracking Signal Selector (Option 3)
Output
tracking
option 3 is used when the controller
is configured
to
be used as a remotely
controlled
output
tracking
controller.
This
occurs when a second
signal received
at Al4 is to be passed
directly
through
the DPRSOO and used as the output
signal to the final control
device.
As illustrated,
when the discrete
input signal is active,
the
controller
takes the analog
signal at Al4 and retransmits
it directly
through
analog
output A01 to the control
valve. With this selection
active,
internal
output signal tracking
is automatically
achieved
for the
internal
loop.
Option
3 should
be selected
when a remote
analog
signal
is to be
retransmitted
through
the controller
to the final control
device
based
on a discrete
switching
signal.
The controller's
output signal can be
made to track a given analog
input signal connected
to Al4, providing
output
tracking
when the discrete
is active.
When output tracking
is enabled,
the output signal at A01 = (A14 +
delta U). Delta U is defined
as the contribution
from the controller
during
regulation
(max f 10%).
The user selects
this function
with FCODE
115, Option
3. The
controller
will track only when the controller
is in the AUTO
mode and
the discrete
input at DII is active.
If the controller
is in the MANUAL
mode,
the discrete
input has no effect on the controller
switching
action and the controller
remains
manually
adjustable.
The output tracking
function
cannot be used with positioning
motor
(raise/lower)
pulse outputs,
Tracking;
Sigh
S&to;
(Al4)
4
Min selection
enabled
5
Max selection
enabled
6
UM6.1:DPR900'9102