Fisher DPR900 User Manual page 63

Integral controller
Table of Contents

Advertisement

Configuration
5-9
The user must press the M button to control the
output signal manually
even though
a discrete
input may have switched
the controller
to manual
mode.
The manual
mode yellow increase
/decrease
buttons
only light after pressing
the M
button to indicate
that manual
control
is possible.
When output signals
are remotely
controlled,
pressing
the M button does not light these two
buttons,
indicating
that they are not locally
adjustable.
Use FCODE
110 to select the function
and the input signal
line, Dll or
Dl2.
Function
FCODE
Option
NO
Default
Selected
VallK?
Value
EXtWlal
110
Disabled
0
0
A/M Track
AutolManualmrack
switching
via DII
1
Switching
Auto/Manual~rackswitchingvia
D12 2
-I
Use FCODE
111 to select the external
remote/local
switching
option.
Function
FCODE
Option
NO
Default
Selected
V&e
Value
EXtfXflal
111
Disabled
0
0
WL
Remote/Local
switching
via DII
1
Switching
Remote/Local
switching
via Dl2
2
Use FCODE
112 to select the option for forced control
of the output
signal via Dll or Dl2.
Function
FCODE
Option
No
Default
Selected
Value
V&B
Forced
112
Disabled
0
0
output
Dll, applies
in Auto/Manual
1
Control
Dl2, applies
in Auto/Manual
2
Dll, applies in Auto only
3
Dl2, applies in Auto only
4
While the external
discrete
switching
signal is
active,
it is not possible
to return to the auto mode
manually.
Change
1 -September
1991
lJM6.1:DPR900:9102